Fire Alarm Panel



Fire Alarm Panel   Next >>

Product Code : 22

Product Specification
Fire Alarm Panels
Multi-protocol Fire Alarm Control Panel.

Features
  • Multi Protocol

  • Modular concept

  • Simple, robust design

  • Intuitive to use

  • Easy to maintain

  • Easy to expand

  • Easy to network

  • Easy to install

  • Easy to configure.

The ZX2e is an intelligent fire alarm control panel. It has been designed and constructed around proven and reliable microprocessor technology. This simple approach has produced a modular, scaleable fire alarm platform suitable for protecting all types of premises.

The ZX2e control panel supports a total of five industry leading protocols, allowing fire detection devices to be independently selected based on performance or aesthetic appeal. The ZX series control panels seamlessly integrates with Apollo (Xplorer, XP95 & Discovery), Hochiki ESP, Nittan, Morley-IAS and System Sensor detection device protocols.

Designed for maximum flexibility the ZX2e control panel is supported by a complete suite of peripherals and software tools. Information on the location of fires, faults and system status can easily be displayed or printed in multiple locations. Integration to Voice Evacuation Systems, paging systems and third party control systems is supported through a range of peripheral interface units.

This adaptability, support and intelligence means that the ZX2e is suitable for new projects, system expansions, retrofits and system upgrades in all application areas. Offices, industrial units, multistorey buildings, entertainment venues, industrial plants and hospitals are a few of the many applications that can benefit from the features of the ZX2e intelligent multi-protocol fire alarm control panel.

Technical Specifications
Operating Voltage:
230V 50Hz ac
(+10%, -15% voltage tolerance)

Max. PSU Rating:
2.5 Amps total, comprising:
Battery Charger: 0.7 Amps
Internal & External Loads: 1.8 Amps.

Note- Remember to use loop and battery calculator to check system and battery loading.

Standby Batteries:
24V sealed lead acid batteries
Minimum Capacity: 2x 12V 6Ah (internally fitted)
Maximum Capacity: 2x 12V 12Ah (internally fitted)
Maximum Capacity: 2x 12V 17Ah (externally fitted)

Power Supply:
Input(s): 24V and 7Vac
(from integral mains transformer)
Output(s):  24Vdc nominal (26.5 - 19.5 Vdc)

Dimensions (mm):
400 x 400 x 135 (H x W x D)

Weight:
10 kg without batteries
18.5 kg with 2x 12Ah batteries.

Environmental Operating Limits:
Temperature: 0ºC to +40ºC
Humidity: 85% non-condensing, maximum

Construction:
Sheet steel painted, sealed to IP30

Cable Entry:
14 x 20mm knock-outs in top of cabinet
2 x 20mm knock-outs in bottom of cabinet.

Loop Capacity:
1 to 2 loops expandable

Apollo, Nittan and Hochiki Protocols:
Max. 126 devices (detectors and modules) per loop.

Morley-IAS and System Sensor Protocols:
Max. 99 sensor and 99 module addresses per loop.

Note : Mulitiple sensor protocols cannot be used in the panel simultaneously.

Zones:
Up to 20 zones with individual LED indicators. A maximum 200 can be programmed with up to 180 software zones with no LED indication.

Internal Sounder:
Intermittent buzzer (fault condition).
High-pitched continuous buzzer (fire condition).

External Outputs:

Sounder Outputs: 2 programmable outputs. Open and short circuit monitoring. 1A maximum per output.
Auxiliary Relays: EN54 format at 1 fault relay and 1 programmable relay voltage free, changeover outputs Contacts rated at 24V ac/dc, 1A, 0.6 pF maximum.

User Controls:
MUTE, ACCEPT, SILENCE/RESOUND, SOUND ALARMS & RESET

Programming Controls:
Alphanumeric multi-level keypad with 15 keys and 3 control keys:
(YES), (CANCEL/ESC), (ENTER)

LED type general panel status indicators:
FIRE, FAULT, ACCEPTED, DISABLEMENT, TEST, SOUNDER FAULT, DELAYED MODE, RELAYS DISABLED, EARTH FAULT, SYSTEM/CPU FAULT, SOUNDERS DISABLED, ALARMS SILENCED, SUPPLY FAULT, POWER.

LED type zone Indicators (for 20 zones):
FIRE, FAULT/TEST/DISABLED

Display:
2x40-character LCD alphanumeric display with back-light.

Serial Interface:
2 serial ports with connections for optional RS485 or RS232 plug-in communication cards.

Networking:
Maximum 99 panels can be networked using a Master Network and connected Sub-Networks.

Approvals:
CE & LPCB (Ref: 429a).

Other Products in 'Fire Alarm Systems' category
Fire Alarm Panels
Fire Alarm Panels
Plug in Smoke Detector
Plug in Smoke Detector
Intelligent Thermal Detector
Intelligent Thermal Detector
 
<< Back
 
SECURITY VISION
9, Anand Vaibhav, 1st Floor, N.C. Kelkar Road, Opp. Shivaji Mandir, Dadar (W), Mumbai - 400028, Maharashtra, India
Phone:91-22-24322727
Fax:91-22-24324747
Send Mail   Send SMS   
Key Personnel
Mr. Shashank Patil (Partner)
Mobile:+919223362727
Mr. Bipin Ayare (Chief Engineer)
Mobile:+919223369571



Translate In : View in English View in Spanish View in French View in German View in Italian View in Chinese (Simplified) View in Japanese View in Korean View in Arabic View in Portuguese
Copyright © 2011-12 by SECURITY VISION All Rights Reserved.